Inverter Connected to Three-Phase Grid – Deye 60-70-75-80k
Deye 60/70/75/80K
Product Features
- 4 MPP Trackers, Maximum Efficiency up to 98.7%
- Voltage and Frequency Support Application
- String Smart Monitoring (Optional)
- Wide Output Voltage Range
- Anti-PID Function (Optional)
- Type II DC/AC SPD
| Model | 60K | 70K | 75K | 80K |
|---|---|---|---|---|
| Input Side | ||||
| Max. DC Input Power (kW) | 78 | 91 | 97.5 | 104 |
| Max. DC Input Voltage (V) | 1100 | |||
| Start-up DC Input Voltage (V) | 250 | |||
| MPPT Operating Range (V) | 200~850 | |||
| Max. DC Input Current (A) | 40+40+40+40 | |||
| Max. Short Circuit Current (A) | 60+60+60+60 | |||
| No.of MPP Trackers | 4 | |||
| No.of Strings per MPP Tracker | 3+3+3+3 | 4+4+4+4 | ||
| Output Side | ||||
| Rated Output Power (kW) | 60 | 70 | 75 | 80 |
| Max. Active Power (kW) | 66 | 77 | 82.5 | 88 |
| Nominal Output Voltage / Range (V) | 3L/N/PE 220/380V, 230/400V | |||
| Rated Grid Frequency (Hz) | 50 / 60 (Optional) | |||
| Operating Phase | Three phase | |||
| Rated AC Grid Output Current (A) | 90.9/87 | 106.1/101.5 | 113.6/108.7 | 121.2/115.9 |
| Max. AC Output Current (A) | 100/95.7 | 116.7/111.6 | 125/119.6 | 133.3/127.5 |
| Output Power Factor | 0.8 leading to 0.8 lagging | |||
| Grid Current THD | <3% | |||
| DC Injection Current (mA) | <0.5% | |||
| Grid Frequency Range | 45~55 or 55~65 (Optional) | |||
| Efficiency | ||||
| Max. Efficiency | 98.7% | |||
| Euro Efficiency | 98.3% | |||
| MPPT Efficiency | >99% | |||
| Protection | ||||
| DC Reverse-Polarity Protection | Yes | |||
| AC Short Circuit Protection | Yes | |||
| AC Output Overcurrent Protection | Yes | |||
| Output Overvoltage Protection | Yes | |||
| Insulation Resistance Protection | Yes | |||
| Ground Fault Monitoring | Yes | |||
| Anti-islanding Protection | Yes | |||
| Temperature Protection | Yes | |||
| Integrated DC Switch | Yes | |||
| Remote software upload | Yes | |||
| Remote change of operating parameters | Yes | |||
| Surge protection | DC Type II / AC Type II | |||
| General Data | ||||
| Size (mm) | 700W×575H×297D | |||
| Weight (kg) | 60 | |||
| Topology | Transformerless | |||
| Internal Consumption | <1W (Night) | |||
| Running Temperature | -25~65°C, >45°C derating | |||
| Ingress Protection | IP65 | |||
| Noise Emission (Typical) | ≤50 dB | ≤55 dB | ||
| Cooling Concept | Smart cooling | |||
| Max. Operating Altitude Without Derating | 2000m | |||
| Warranty | 5 years | |||
| Grid Connection Standard | VDE4105, IEC61727/62116, VDE0126, AS4777.2, CEI 0 21, EN50549-1, G98, G99, C10-11, UNE217002, NBR16149/NBR16150 | |||
| Operating Surroundings Humidity | 0-100% | |||
| Safety EMC / Standard | IEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2 | |||
| Features | ||||
| DC Connection | MC-4 mateable | |||
| AC Connection | IP65 rated plug | |||
| Display | LCD 240x160 | |||
| Interface | RS485/RS232/Wifi/LAN | |||