Inverter Connected to Three-Phase Grid – Deye 40-45-50k
Deye 40/45/50K
Product Features
- 4 MPP Trackers, Maximum Efficiency up to 98.7%
- Voltage and Frequency Support Application
- String Smart Monitoring (Optional)
- Wide Output Voltage Range
- Anti-PID Function (Optional)
| Model | 40K | 45K | 50K |
|---|---|---|---|
| Input Side | |||
| Max. DC Input Power (kW) | 52 | 58.5 | 65 |
| Max. DC Input Voltage (V) | 800 | ||
| Start-up DC Input Voltage (V) | 250 | ||
| MPPT Operating Range (V) | 200~700 | ||
| Max. DC Input Current (A) | 40+40+40+40 | ||
| Max. Short Circuit Current (A) | 60+60+60+60 | ||
| No.of MPP Trackers | 4 | ||
| No.of Strings per MPP Tracker | 4+4+4+4 | ||
| Output Side | |||
| Rated Output Power (kW) | 40 | 45 | 50 |
| Max. Active Power (kW) | 44 | 45 | 50 |
| Nominal Output Voltage / Range (V) | 3L/N/PE 127V/220V | 3L/N/PE 133V/230V | |
| Rated Grid Frequency (Hz) | 50 / 60 (Optional) | ||
| Operating Phase | Three phase | ||
| Rated AC Grid Output Current (A) | 100.3 | 112.8 | 125.4 |
| Max. AC Output Current (A) | 100.3 | 112.3 | 125.4 |
| Output Power Factor | 0.8 leading to 0.8 lagging | ||
| Grid Current THD | <3% | ||
| DC Injection Current (mA) | <0.5% | ||
| Efficiency | |||
| Max. Efficiency | 98.7% | ||
| Euro Efficiency | 98.3% | ||
| MPPT Efficiency | >99% | ||
| Protection | |||
| DC Reverse-Polarity Protection | Yes | ||
| AC Short Circuit Protection | Yes | ||
| AC Output Overcurrent Protection | Yes | ||
| Output Overvoltage Protection | Yes | ||
| Insulation Resistance Protection | Yes | ||
| Ground Fault Monitoring | Yes | ||
| Anti-islanding Protection | Yes | ||
| Temperature Protection | Yes | ||
| Integrated DC Switch | Yes | ||
| Remote software upload | Yes | ||
| Remote change of operating parameters | Yes | ||
| Surge protection | DC Type II / AC Type II | ||
| General Data | |||
| Size (mm) | 700W×575H×297D | ||
| Weight (kg) | 60 | ||
| Topology | Transformerless | ||
| Internal Consumption | <1W (Night) | ||
| Running Temperature | -25~65°C, >45°C derating | ||
| Ingress Protection | IP65 | ||
| Noise Emission (Typical) | ≤55 dB | ||
| Cooling Concept | Smart cooling | ||
| Max. Operating Altitude Without Derating | 2000m | ||
| Warranty | 5 years | ||
| Grid Connection Standard | VDE4105, IEC61727/62116, VDE0126, AS4777.2, CEI 0 21, EN50549-1, G98, G99, C10-11, UNE217002, NBR16149/NBR16150 | ||
| Operating Surroundings Humidity | 0-100% | ||
| Safety EMC / Standard | IEC/EN 61000-6-1/2/3/4, IEC/EN 62109-1, IEC/EN 62109-2 | ||
| Features | |||
| DC Connection | MC-4 mateable | ||
| AC Connection | IP65 rated plug | ||
| Display | LCD 240x160 | ||
| Interface | RS485/RS232/Wifi/LAN | ||